Products

SAFEPATH DoD Facility Communications System

VoiceEvacSystem_SP40.jpg

SP40S-D - Supervised Voice Evacuation System

Designed for Department of Defense (DoD) facilities, Cooper Notification’s SAFEPATH (SP40S-D) is an Emergency Voice Evacuation System with 24 VDC battery backup. The multi-use system can function as an evacuation, emergency messaging, paging, personnel alerting, and background music delivery system. The SP40S-D integrates with fire alarm systems and provides full control of building audible and visual notification appliances.

To meet the UFC requirement for automatic alarm audible shutoff after 10 minutes, the SP40S-D includes a 10-minute time-out feature, which automatically deactivates Fire and Emergency digital voice (DV) messages inputs 1 - 6 after 10 minutes. Alarm DV messages inputs 7 and 8 do not automatically time out.

  • Approvals: UL Standard 864, 9th edition, UL Standard 1711
  • Meets UFC 10-minute message time-out requirement
  • NFPA 72, OSHA 1910.165 and ADA Compliant
  • Expandable for larger system requirements
  • 8 digitally recorded voice messages with live microphone override
  • Supervised NAC speaker and strobe circuits
Items File(s) Links
Specification Sheet
SP40S-D System
Instruction Sheet SAFEPATH - P84714
Agency Approvals  UL