iDP-210 Feeder Protection Relay

Idea_and_IdeaPlus_Relays.jpg

The iDP-210 is a member of Eaton's Cooper Power™ series Edison™ Idea™ line of protective relays. The iDP-210 is a full-featured relay suitable for a variety of protection applications including feeder protection, reclosing, synch-check, frequency-based load shedding, reverse power, overcurrent, over/under voltage and frequency. The iDP-210 also provides advanced power quality, metering, control, communication and PLC functions.

 

Frequency 50/60 Hz
Current Inputs Four current input channels
INominal = 5A, Icontinuous = 15A, I3sec = 150A, I1sec = 300A
Range of overcurrents settings 0.1 A to 90 A
Burden < 0.2VA at 5A
Primary DC Resistance 3.4 mΩ
Error % < 0.3% over operating temperature
INominal = 1A, Icontinuous = 3.2A, I3sec = 30 A, I1sec = 100A
Range of overcurrents settings 0.02 A to 18 A
Burden < 0.2VA at 1A
Primary DC Resistance 52.1 mΩ
Error % < 0.3% over operating temperature
Digital Inputs (Optically Isolated) 9 – 150 VDC [24 VDC power supply]
36 – 150 VDC [48 VDC power supply]
90 – 300 VDC [120 VAC / 125 VDC power supply]
165 – 300 VDC [240 VAC / 250 VDC power supply]
Nominal current draw of 2.5 mA, minimum operating time of 15 msec

Features

Highlights

  • Add functions and features using the Idea Workbench
  • Cooper’s exclusive ICSF (Incipient Cable Splice Failure) Detection System for underground cables
  • Virtual Test Set event record simulator
  • Relay Replay: The “what-if” analysis tool
  • Interactive oscillography
  • Instantaneous, Demand and Energy Metering
  • Harmonics and THD metering
  • Load Encroachment and Cold Load Pickup Logic
  • Breaker Health Monitoring
  • Sequence of Events Recording
  • Distance-to-fault calculation
  • 6 Voltage Input option
  • Eight setting groups
  • DNP 3.0 and Modbus protocols standard

Protective Functions

  • Fuse-fail detection (27FF)
  • Reverse power (32)
  • Phase instantaneous, definite time, and inverse time overcurrent (50/51)
  • Ground instantaneous, definite time, and inverse time overcurrent (50N/51N)
  • Negative-sequence instantaneous, definite time, and inverse time overcurrent (50Q/51Q)
  • Multiple-shot programmable reclosing (79)
  • Predictive Sync-check (25) with anti-motoring
  • Breaker fail-to-trip and fail-to close detection (50BF)
  • Directional phase, ground and negative sequence elements (67P, 67N, 67Q)
  • Directional neutral (sensitive earth fault optional) protection (50G/50SEF)
  • Multiple-Step over/under frequency elements with voltage and current supervision (81)
  • Over/under voltage elements (27/59)
  • Sequence overvoltage (59P, 59Q, 59N)