EBM Series Explosionproof Disconnect Switches

EBM Disconnect Switches are used:
- To disconnect motor, lighting and other circuits
- In locations made hazardous by the presence of flammable gases or vapors or ignitable dusts
- To provide disconnect means and short circuit protection (fusible version)
- On switch racks or other assemblies where it is desired that motor control be centrally located
Amperage Ratings | 30; 60; 100A |
Voltage | 600 VAC heavy duty |
Body, Cover and Operating Handle Material | Copper-free aluminum |
Operating Shaft and Bushing Material | Stainless steel |
Interior Parts Material | Sheet steel, electrogalvanized |
Cover Bolt, Washer and Retractile Spring Material | Stainless steel |
Hinge Material | Stainless steel |
Features
- Rugged corrosion-resistant cast copper-free aluminum construction (less than 0.4 of 1%)
- Switch operating handle is located through the right side wall of the body, permits visual confirmation of correct alignment and operation
- Total compliance to the wiring end room requirements of the National Electrical Code®
- Semi-clamshell enclosure design, with an external flanged ground joint between body and cover makes interior components more accessible
- Minimum enclosure-to-enclosure spacing with little interference between the opened cover and an adjacent enclosure
- Stainless steel hinges allow the cover to swing well out of the way
- Stainless steel quick release captive hex head cover bolts; stainless steel springs provide clear indication that cover bolts are fully retracted from the body
- Switch operating handle can be padlocked in either the "ON" or "OFF" position
- Neoprene cover gasket permanently attached to the cover seals out moisture
- Bodies have top and bottom drilled and tapped conduit entrances for power and conduits; removable reducers are supplied as standard, to accommodate smaller size conduits; all conduit entrances are plugged
- Tap-on mounting feet