Low-Peak Class L time-delay fuse in ratings from 601 to 6000 amps. Time-delay four (4) seconds (minimum) at 500% rated amps allows closer sizing on large motor loads combined with Class L current limitation.
Selective coordination ratio of 2:1 within the Low-Peak family (LPJ Class J, NPN 250V Class RK1, LPS 600V Class RK1) prevents electrical shutdowns from extending beyond the failed circuit.
300kA RMS Sym. Interrupting rating provides adequate ratings without obsolesence for all electrical systems big and small.
| Catalog Number | KRP-C__SP |
| Dimensions | See Data Sheets # 1008 (601-200 amps) & # 1009 (2001-6000 amps) |
| Volts | 600Vac (or less), 300Vdc (601-2000A) |
| Amps | 601-6000 For 150-600 amps in an 800 amp Class L fuse size, see KRP-CL Data Sheet # 1016 |
| IR | 300kA RMS Sym., 100kA DC |
| Agency Information | CE, UL Listed- Special Purpose (meets all performance requirements of UL Standard 248-10 for Class L fuses), Guide JFHR, File E56412, CSA Certified (200k AIR), Class 1422-02, File 53787, Class L per CSA C22.2, No. 248.10. |
| Typical Applications | • Large Distribution Switchboards • Power Panelboards • Large Machinery Disconnects |