XL size PV fuses

bus-iec-solar-pv-fuse-xl-size-220.jpg

Up to 1500Vdc Meets The Demand for Greater Capacity and Efficiency

UL, CCC and IEC (gPV) certified to support a global application design, removing additional certification requirements, this range of XL size photovoltaic fuses are specifically designed for protecting and isolating photovoltaic array combiners and disconnects. These fuse links are capable of interrupting low overcurrents associated with faulted PV systems (reverse current, multi-array fault).

Compatible with Bussmann PV XL base range (see data sheet No. 10066)

Product profile No. 3214

Data sheet no. 10201

UL certifications

2-D PDF CAD drawings

Solar circuit protection application note no. 10191


RoHS compliant

Part Numbers Bladed Version Part Numbers Bolted Version Body Size Current Rating (amps) Rated Voltage Rated Breaking Capacity I2t (A2s) Pre-Arcing I2t (A2s) Total at Rated Voltage  Watts Loss 0.8In Watts Loss In

1000Vdc

01XL Size
PV-63A-01XL PV-63A-01XL-B 01 63 1000Vdc 50kA 260 1900 13 24
PV-80A-01XL PV-80A-01XL-B 01 80 1000Vdc 50kA 490 3600 17 29
PV-100A-01XL PV-100A-01XL-B 01 100 1000Vdc 50kA 870 6300 18 32
PV-125A-01XL PV-125A-01XL-B 01 125 1000Vdc 50kA 1930 13,900 20 40
PV-160A-01XL PV-160A-01XL-B 01 160 1000Vdc 50kA 3900 28,100 22 44
1XL Size
PV-200A-1XL* PV-200A-1XL-B* 1 200 1000Vdc 33kA 9400 27,260 31 54
2XL Size
PV-160A-2XL PV-160A-2XL-B 2 160 1000Vdc 50kA 2780 21,000 25 44
PV-200A-2XL PV-200A-2XL-B 2 200 1000Vdc 33kA 4950 37,000 28 50
PV-250A-2XL PV-250A-2XL-B 2 250 1000Vdc 33kA 9450 70,000 34 60
PV-315A-2XL PV-315A-2XL-B 2 315 1000Vdc 33kA 16,600 123,000 40 66
PV-350A-2XL PV-350A-2XL-B 2 350 1000Vdc 50kA 26,000 192,000 42 68
PV-355A-2XL PV-355A-2XL-B 2 355 1000Vdc 50kA 26,000 192,000 42 68
3L Size
PV-350A-3L PV-350A-3L-B 3 350 1000Vdc 50kA 31,000 161,200 40 65
PV-400A-3L PV-400A-3L-B 3 400 1000Vdc 50kA 44,500 231,400 48 82
PV-500A-3L PV-500A-3L-B 3 500 1000Vdc 50kA 85,000 442,000 50 85
PV-600A-3L
PV-600A-3L-B 3 600 1000Vdc 50kA 137,000 712,400 80 108
PV-630A-3L PV-630A-3L-B 3 630* 1000Vdc 50kA 137,000 712,400 92 118

* 630A Thermally rated to UL only.

Part Numbers Bladed Version Part Numbers Bolted Version Body Size Current Rating (amps) Rated Voltage Rated Breaking Capacity I2t (A2s) Pre-Arcing I2t (A2s) Total at Rated Voltage  Watts Loss 0.8In Watts Loss In
1500Vdc
01XL Size
PV-50A-01XL-15 PV-50A-01XL-B-15 01 63 1500Vdc 30kA 280 1450 6 26
PV-63A-01XL-15 PV-63A-01XL-B-15 01 63 1500Vdc 30kA 420 2250 17 28
PV-80A-01XL-15 PV-80A-01XL-B-15 01 80 1500Vdc 33kA 950 5000 18 30
PV-100A-01XL-15 PV-100A-01XL-B-15 01 100 1500Vdc 30kA 1250 6500 22 38
PV-125A-01XL-15 PV-125A-01XL-B-15 01 125 1500Vdc 30kA 2200 11,500 27 48
PV-160A-01XL-12 PV-160A-01XL-B-12 01 160 1200Vdc 33kA 5000 19,000* 24 48
1XL Size
PV-100A-1XL-15 PV-100A-1XL-B-15 1 100 1500Vdc 30kA 1250 6000 24 43
PV-125A-1XL-15 PV-125A-1XL-B-15 1 125 1500Vdc 30kA 1950 9360 25 52
PV-160A-1XL-15 PV-160A-1XL-B-15 1 160 1500Vdc 30kA 4200 20,160 30 58
PV-200A-1XL-15 PV-200A-1XL-B-15 1 200 1500Vdc 30kA 9400 45,120 31 61
2XL Size
PV-125A-2XL-15 PV-125A-2XL-B-15 2 125 1500Vdc 30kA 2200 11,000 23 43
PV-160A-2XL-15 PV-160A-2XL-B-15 2 160 1500Vdc 30kA 5000 25,000 26 50
PV-200A-2XL-15 PV-200A-2XL-B-15 2 200 1500Vdc 30kA 9300 36,000 28 56
PV-250A-2XL-15 PV-250A-2XL-B-15 2 250 1500Vdc 30kA 13,700 68,000 38 72
3L Size
PV-250A-3L-15 PV-250A-3L-B-15 3 250 1500Vdc 30kA 20,000 61,000 35 62
PV-315A-3L-15 PV-315A-3L-B-15 3 315 1500Vdc 30kA 38,000 116,000 40 72
PV-355A-3L-15 PV-355A-3L-B-15 3 355 1500Vdc 30kA 44,500 136,000 46 84
PV-400A-3L-15
PV-400A-3L-B-15 3 400 1500Vdc 30kA 58,000 177,000 50 91

* At 1200Vdc for 160A 01XL size.