10x38 mm PV fuses

A range 10x38mm, 1000Vdc PV fuses for the protection and isolation of photovoltaic strings. The fuses are specifically designed for use in PV systems with extreme ambient temperature, high cycling and low fault current conditions (reverse current, multi-array fault) string arrays.

Available with four mounting styles for application flexibility:

  1. Cylindrical ferrule
  2. Bolt Fixing
  3. Single and double pin PCB tabs
  4. In-line crimp terminals

For a complete in-line PV fuse assembly, see HPV.

Data sheet no. 10121

UL Certifications

Solar circuit protection application guide no. 10191


RoHS compliant

  Amps Volts
(Vdc)
Energy Integrals I2t (A2s) Watts Loss (W)
Pre-Arcing Total @ 1000V 0.8In In
Cylindrical Ferrule
PV-1A10F 1 1000 0.15 0.4 0.8 1.5
PV-2A10F 2 1000 1.2 3.4 0.6 1
PV-3A10F 3 1000 4 11 0.8 1.3
PV-3-5A10F 3.5 1000 6.6 18 0.9 1.4
PV-4A10F 4 1000 9.5 26 1 1.5
PV-5A10F 5 1000 19 50 1 1.6
PV-6A10F 6 1000 30 90 1.1 1.8
PV-8A10F 8 1000 3 32 1.2 2.1
PV-10A10F 10 1000 7 70 1.2 2.3
PV-12A10F 12 1000 12 120 1.5 2.7
PV-15A10F 15 1000 22 220 1.7 2.9
PV-20A10F 20 1000 34 350 2.1 3.6
Bolt Fixing
PV-1A10-T 1 1000 0.15 0.4 0.8 1.5
PV-2A10-T 2 1000 1.2 3.4 0.6 1
PV-3A10-T 3 1000 4 11 0.8 1.3
PV-3-5A10-T 3.5 1000 6.6 18 0.9 1.4
PV-4A10-T 4 1000 9.5 26 1 1.5
PV-5A10-T 5 1000 19 50 1 1.6
PV-6A10-T 6 1000 30 90 1.1 1.8
PV-8A10-T 8 1000 3 32 1.2 2.1
PV-10A10-T 10 1000 7 70 1.2 2.3
PV-12A10-T 12 1000 12 120 1.5 2.7
PV-15A10-T 15 1000 22 220 1.7 2.9
PV-20A10-T 20 1000 34 350 2.1 3.6
PCB Fixing Single Pin
PV-1A10-1P 1 1000 0.15 0.4 0.8 1.5
PV-2A10-1P 2 1000 1.2 3.4 0.6 1
PV-3A10-1P 3 1000 4 11 0.8 1.3
PV-3-5A10-1P 3.5 1000 6.6 18 0.9 1.4
PV-4A10-1P 4 1000 9.5 26 1 1.5
PV-5A10-1P 5 1000 19 50 1 1.6
PV-6A10-1P 6 1000 30 90 1.1 1.8
PV-8A10-1P 8 1000 3 32 1.2 2.1
PV-10A10-1P 10 1000 7 70 1.2 2.3
PV-12A10-1P 12 1000 12 120 1.5 2.7
PV-15A10-1P 15 1000 22 220 1.7 2.9
PV-20A10-1P 20 1000 34 350 2.1 3.6
PCB Fixing Double Pin
PV-1A10-2P 1 1000 0.15 0.4 0.8 1.5
PV-2A10-2P 2 1000 1.2 3.4 0.6 1
PV-3A10-2P 3 1000 4 11 0.8 1.3
PV-3-5A10-2P 3.5 1000 6.6 18 0.9 1.4
PV-4A10-2P 4 1000 9.5 26 1 1.5
PV-5A10-2P 5 1000 19 50 1 1.6
PV-6A10-2P 6 1000 30 90 1.1 1.8
PV-8A10-2P 8 1000 3 32 1.2 2.1
PV-10A10-2P 10 1000 7 70 1.2 2.3
PV-12A10-2P 12 1000 12 120 1.5 2.7
PV-15A10-2P 15 1000 22 220 1.7 2.9
PV-20A10-2P 20 1000 34 350 2.1 3.6
In-line with Crimp Terminal
PV-1A10F-CT 1 1000 0.15 0.4 0.8 1.5
PV-2A10F-CT 2 1000 1.2 3.4 0.6 1
PV-3A10F-CT 3 1000 4 11 0.8 1.3
PV-3-5A10F-CT 3.5 1000 6.6 18 0.9 1.4
PV-4A10F-CT 4 1000 9.5 26 1 1.5
PV-5A10F-CT 5 1000 19 50 1 1.6
PV-6A10F-CT 6 1000 30 90 1.1 1.8
PV-8A10F-CT 8 1000 3 32 1.2 2.1
PV-10A10F-CT 10 1000 7 70 1.2 2.3
PV-12A10F-CT 12 1000 12 120 1.5 2.7
PV-15A10F-CT 15 1000 22 220 1.7 2.9
PV-20A10F-CT 20 1000 34 350 2.1 3.6