North American — FWP 700V: 5-1200A

Catalog Number FWP-_B (5 to 100 amps), FWP-_A (125 to 1200 amps)
Dimensions See data sheet no. 720012
Volts 700 Vac/dc
Amps - 5 to 100 A (FWP-_B)
- 125 to 1200 A (FWP-_A)
Interrupting rating - 200 kA RMS Sym.
- 50 kA @700 Vdc (5 - 100 A and 700 - 800 A)
- 10 kA @ 700 Vdc (125 - 600 A)
Agency information - CE
- UL Recognized JFHR2 E91958 (5 - 100 A and 700 - 1200 A)
- UL Recognized JFHR2 E56412 (125 - 600 A)
- CSA Component Acceptance File Class 1422 (53787 for 5 - 800 A)
Typical applications - DC common bus
- DC drives
- Power converters/rectifiers
- Reduced voltage starters

Features

  • Excellent DC performance
  • Low arc voltage and low energy let-through (I2t)
  • Superior cycling capability