Global Modular Fuse Holders

Finger-safe DIN-Rail mount fuse holders protect your electrical system and simplify installation

  • Easy color coding for use: yellow for PV, red for IEC, and black for UL applications
  • Finger-safe, high SCCR rated, Class CC and midget holders with indicator options
  • Agency ratings up to 1000Vdc for use with solar PV fuses
  • Available remote PLC indication with the CH-PLC module
  • Rated for use with 75ºC or 90ºC wire, fine stranded wire, spade terminals and with comb-bus bars. Use any higher temperature rated wire with appropriate derating
  • Complete range of UL Listed and high SCCR rated 1-phase and 3-phase finger-safe comb busbars and power feed lugs
  • Optional hex head terminal screws; order by adding "-H" suffix to the catalog number, e.g., CHM1DU-H

Product profile No. 3184

Data sheet No. 10430

CAD drawings

Product change notice

CHPV product change notice

What's changed

FAQs

REACH declarations and REACH/RoHs materials compliance documents

RoHS query search engine

Agency cards

Old modular fuse holder data sheet No. 2053

Catalog Number CHPV_ (10x38 photovoltaic fuse), CHM_ (midget fuse), CHCC_ (Class CC fuse)
Catalog symbols/versions - CHPV (Photovoltaic)
- CHM (10x38 & Midget)
- CHCC (Class CC)
Volts - 600V (UL)
- 690V (IEC)
- 1000Vdc (PV)
Agency information - UL File E14853 Guide IZLT Listed, IZLT2 Recognized
- CSA: File 47235, CHPV and CHM - Class 6225-30, CHCC - Class 6225-01
SCCR - 200kA (Class CC)
- 200kA (10x38 & Midget)
- 33kA PV
Poles 1, 2, 3, 4 and 3-Pole + Neutral (See tables for details)
Terminal conductor ratings - Solid
- Stranded
- Fine stranded
- Fork lug
- Comb busbar
- Single and dual wire, 75ºC and 90ºC Cu
Mounting 35mm DIN-Rail
Storage and operating temperature range -20ºC to +90ºC (indicating)
-20ºC to +120ºC (non-indicating)

CHPV for 1000V 10x38mm PV fuses

 
Series
& Size
Catalog Numbers
With Indicator
Catalog Numbers
Without Indicator
Voltage
& Current
Agency
Markings
Number
of Poles
Terminal
Rating
SCCR
Rating
Cooper
Bussmann
Fuses
CHPV
CHPV1IU
CHPV1U
UL & IEC;
1000Vdc/30A
UR, CSA,
UL 4248-18,
IEC 60269-1, CCC
1
Solid, Stranded,
Fine Stranded,
Spade Lug,
Comb-Bus Bar;
Single and Dual Wire;
75ºC and 90ºC Cu wire
33kA
Solar
PV Series
CHPV2IU
CHPV2U
2
 

Optional hex head terminal screws; order by adding "-H" suffix to the catalog number, e.g., CHPV1U-H.

CHM for Midget and 10x38mm fuses

 
Series
and size
Catalog numbers
with indication
Catalog numbers
without indication
Voltage
and amps
Agency
markings
Number
of poles
Terminal
rating
SCCR
rating
Bussmann
series fuses
CHM
10x38
and
Midget
CHM1DIU
CHM1DU
UL 600V/30A;
IEC 690V/32A
UR;
IEC 60269-2; CSA; CCC
1
Solid,
Stranded,
Fine Stranded,
Spade Lug,
Comb-Bus Bar;
Single and Dual Wire;
 75ºC and 90ºC Cu wire
200kA
rms sym
FNQ, KLM,
FNM, KTK,
BAF, FWA,
PVM,
C10 SERIES,
AGU,
BAN, FWC
CHM2DIU
CHM2DU
2
CHM3DIU
CHM3DU
3
CHM4DIU
CHM4DU
4
CHM1DNIU
CHM1DNU
IEC 60269-2
1 Pole +
1 Neutral
CHM3DNIU
CHM3DNU
3 Pole +
1 Neutral
CHM1DI-48U
 
UL 48Vdc/30A;
IEC 48Vdc/32A
UR; IEC; 60269-2; CSA; CCC
1
 
CHM1DNXU
IEC 690V/32A
IEC 60269-2
1 Neutral
N/A
N/A

Optional hex head terminal screws; order by adding "-H" suffix to the catalog number, e.g., CHM1DU-H.

CHCC for Class CC fuses

 
Series
and size
Catalog numbers
with Indication
Catalog numbers
without Indication
Voltage
and amps
Agency
markings
Number
of poles
Terminal
rating
SCCR
rating
Bussmann
series fuses
CHCC
Class CC
CHCC1DIU
CHCC1DU
UL 600V/
30A
UL; CSA; CCC
1
Solid,
Stranded,
Fine Stranded,
Spade Lug,
Comb-Bus Bar;
Single and Dual Wire;
75ºC and 90ºC Cu wire
200kA
rms sym
LP-CC,
FNQ-R,
KTK-R
CHCC2DIU
CHCC2DU
2
CHCC3DIU
CHCC3DU
3
 
CHCC1DI-48U
UL 48Vdc/
30A
1

Optional hex head terminal screws; order by adding "-H" suffix to the catalog number, e.g., CHCC1DU-H.