CCP for Class CC, Supplemental and 10x38 mm fuses

The revolutionary next generation Bussmann series Compact Circuit Protector for UL® Class CC, UL Supplemental and IEC® 10x38 mm fuses delivers the smallest footprint compared to any Class CC disconnect solution — requiring up to 38% less space.

CCP2 product profile no. 10793

CCP2 data sheet no. 10789

FAQs no. 10794

Install instructions no. 3A3599

Selector and pistol handle install instructions no. 3A3695

Legacy CCP data sheet no. 1157

Legacy product end of life notice and recommended replacements

 

Contact Information

Ordering: (636) 527-3877

Technical Support: (636) 527-1270

E-mail

Catalog numbers and general ratings

See data sheet no. 10789 for details.

Catalog no. Poles Description Amps Volts SCCR Max horsepower rating (Vac) Wire type/size*
120 240 480 600
Class CC
CCP2-1-30CC 1 Switch only 30 A 347 Vac 200 kA ½ - - - 75°C Cu/Al, 18-4 AWG, Fork terminal**
CCP2-2-30CC 2 600 Vac - 2 - -
CCP2-3-30CC 3 ¾ 3 5 7.5
CCP2R-2-30CC 2 Switch with right front rotary operation 600 Vac - 2 - -
CCP2R-3-30CC 3 ¾ 3 5 7.5
CCP2RL-2-30CC 2 Switch with left front rotary operation 600 Vac - 2 - -
CCP2RL-3-30CC 3 ¾ 3 5 7.5
CCP2S-2-30CC 2 Switch with right side rotary operation 600 Vac - 2 - -
CCP2S-3-30CC 3 ¾ 3 5 7.5
CCP2SL-2-30CC 2 Switch with left side rotary operation 600 Vac - 2 - -
CCP2SL-3-30CC 3 ¾ 3 5 7.5
UL Supplemental and IEC 10x38 mm
CCP2-1-30M 1 Switch only UL 30 A, IEC 32 A** UL 240 Vac***, IEC 400 Vac*** UL 10 kA***, IEC 120 kA*** N/A N/A N/A N/A 75°C Cu/Al, 18-4 AWG, Fork terminal****
CCP2-2-30M 2
CCP2-3-30M 3
CCP2R-2-30M 2 Switch with right front rotary operation
CCP2R-3-30M 3
CCP2RL-2-30M 2 Switch with left front rotary operation
CCP2RL-3-30M 3
CCP2S-2-30M 2 Switch with right side rotary operation
CCP2S-3-30M 3
CCP2SL-2-30M 2 Switch with left side rotary operation
CCP2SL-3-30M 3
Single-pole DC switches
CCP2-1-DCC 1 UL Class CC 30 A 80 Vdc*** 20 kA*** N/A N/A N/A N/A 75°C Cu/Al, 18-4 AWG, Fork terminal****
CCP2-1-DCM 1 UL supplemental 30 A 80 Vdc*** 10 kA***
IEC 10x38 32 A**

* See box lug terminal conductor data table for details.

** 32 A Class aM, 25 A Class gG.

*** SCCR may be lower, refer to installed fuse data sheet for interrupting rating at applied voltage.

**** Fork terminal with a 4.3 mm gap for a #8-32 stud, 30 A max, insulated flange, wire size 12-10 AWG.