30-100 A CCP for Class CF CUBEFuse

Now with rotary operators and multi-wire lug kits

The revolutionary Bussmann™ series Compact Circuit Protector (CCP) for Class CF Low-Peak™ CUBEFuse™ delivers the smallest footprint compared to any Class J disconnect solution — requiring up to 51% less space.

The CCP is a UL® 98 Listed fused, branch-circuit disconnect that packs up to a 200 kA short-circuit current rating (SCCR) at 600 V to help increase equipment SCCR. These high ratings and compact design make the CCP ideal for industrial control panels, machinery and HVAC applications.

Video

Power of Space brochure no. 10820

CCP product profile no. 10809

CCP data sheet no. 10801

Enclosed CCP product profile no. 10899

Enclosed CCP data sheet no. 10889

Application note no. 7038

CUBEFuse product profile no. 3083

CUBEFuse data sheet no. 9000

FAQs no. 10825

Install sheets

CCPB product profile no. 10270

CCPB data sheet no. 1161

CCD2 non-fused disconnect data sheet no. 10004

Legacy CCP data sheet no. 1157

Legacy CCP-CF end of life notice and recommended replacements

Legacy CCPB-CF end of life notice and recommended replacements

Catalog no. Poles Description Volts SCCR Max Hp rating (Vac)  
          120 240 480 600
30 amp switches
CCP2-1-30CF 1 Switch only 347 Vac/125 Vdc 200 kA AC/100 kA DC 1.5 - - -
CCP2-2-30CF 2 600 Vac/125 Vdc - 3 - -
CCP2-3-30CF 3 600 Vac - 5 15 10
CCP2R-2-30CF 2 Right front rotary, clockwise operated switch 600 Vac/125 Vdc - 3 - -
CCP2R-3-30CF 3 600 Vac - 5 15 10
CCP2RL-2-30CF 2 Left front rotary, clockwise operated switch 600 Vac/125 Vdc - 3 - -
CCP2RL-3-30CF 3 600 Vac - 5 15 10
CCP2S-2-30CF 2 Right side rotary, clockwise operated switch 600 Vac/125 Vdc - 3 - -
CCP2S-3-30CF 3 600 Vac - 5 15 10
CCP2SL-2-30CF 2 Left side rotary, counterclockwise operated switch 600 Vac/125 Vdc - 3 - -
CCP2SL-3-30CF 3 600 Vac - 5 15 10
60 amp switches
CCP2-1-60CF 1 Switch only 347 Vac/125 Vdc* 200 kA AC/100 kA DC 3 - - -
CCP2-2-60CF 2 600 Vac/125 Vdc* - 7.5 - -
CCP2-3-60CF 3 600 Vac - 7.5 20 10
CCP2R-2-60CF 2 Right front rotary, clockwise operated switch 600 Vac/125 Vdc* - 7.5 - -
CCP2R-3-60CF 3 600 Vac - 7.5 20 10
CCP2RL-2-60CF 2 Left front rotary, clockwise operated switch 600 Vac/125 Vdc* - 7.5 - -
CCP2RL-3-60CF 3 600 Vac - 7.5 20 10
CCP2S-2-60CF 2 Right side rotary, clockwise operated switch 600 Vac/125 Vdc* - 7.5 - -
CCP2S-3-60CF 3 600 Vac - 7.5 20 10
CCP2SL-2-60CF 2 Left side rotary, counterclockwise operated switch 600 Vac/125 Vdc* - 7.5 - -
CCP2SL-3-60CF 3 600 Vac - 7.5 20 10
100 amp switches
CCP2-1-100CF 1 Switch only 347 Vac/125 Vdc** 200 kA AC/100 kA DC 5 - - -
CCP2-2-100CF 2 600 Vac/125 Vdc** - 10 - -
CCP2-3-100CF 3 600 Vac - 20 50 40
CCP2R-2-100CF 2 Right front rotary, clockwise operated switch 600 Vac/125 Vdc** - 10 - -
CCP2R-3-100CF 3 600 Vac - 20 50 40
CCP2RL-2-100CF 2 Left front rotary, clockwise operated switch 600 Vac/125 Vdc** - 10 - -
CCP2RL-3-100CF 3 600 Vac - 20 50 40
CCP2S-2-100CF 2 Right side rotary, clockwise operated switch 600 Vac/125 Vdc** - 10 - -
CCP2S-3-100CF 3 600 Vac - 20 50 40
CCP2SL-2-100CF 2 Left side rotary, counterclockwise operated switch 600 Vac/125 Vdc** - 10 - -
CCP2SL-3-100CF 3 600 Vac - 20 50 40
* 125 Vdc for installed fuse amp ratings up to 40 A. 24 Vdc for installed fuse amp ratings from 45 to 60 A.
** 125 Vdc for installed fuse amp ratings up to 80 A, 24 Vdc for installed fuse amp ratings from 90 to 100 A.